TechGen CFU units have been designed for the pharmaceutical industry to control the problem of powder contamination and reduce operator's exposure to powder; namely, the units protect the powder from blowing about and cross-contaminating other areas and products, and protect the operator from inhalation of potentially hazardous pharmaceuticals.
Primarily conceived for the pharmaceutical industry, they can be used whenever there is a risk of dust contamination.
Principle
Air from the H14 HEPA/ULPA filter passes down over the enclosed space, then through two pre-filters and back to the H14 HEPA/ULPA filter plenum chamber. A small absolute filter mounted downstream of the fans generates a loss in the air recycling system, causing an inflow of air between the vinyl curtain and floor.
The vertical air stream carries away powder generated and spilt in the manufacturing process, and passing through the pre-filters is recycled or exhausted via H14 HEPA/ULPA filters. This airflow pattern encourages a floor level air movement to prevent powder drifting through the room, and contamination of sterile products, which are generally kept at least 50 cm from the floor.
Specifications
Body structure fully made in stainless steel AISI 304L press-bent metal sheets with radius of 3 mm for easy cleaning and roughness lower than 0,8 Ra.
Filter protective grids made in AISI 304L stainless steel.Custom dimensions are always available upon request.
Prefiltration stage consisting of G3 filtration cells made in AISI 304L stainless steel fitted with quick-release system and F9 dihedral bag filters in compliance to EN 779.
Filtration stage consisting of main and exhaust H14 HEPA/ULPA filter DUG type with volume control dumper and DEHS test port with typical efficiency of 99.995% MPPS according to CEN EN 1822.
Bag plenum made in technical material for superior air diffusion.
Ventilation is provided by high efficiency electronically commutated double inlet motorblowers ECM DDTAC type.
Pressure control provided by electronic output and analogic visualization by means of Dwyer manometers.
Side containment provided by means of PVC strip curtains or stainless steel side walls.
.